Unit maintenance

Unit maintenance

Class a maintenance
1. Daily:
1) check the daily work of the generator.
2) check generator: Oil plane and coolant plane.
3) whether the generator is damaged or leaked, and whether the belt is loose or worn.
Two. Every week:
1) repeat a daily a class examination.
2) check the air cleaner, clean or replace the air cleaner core.
3) release the fuel tank and the water or sediment in the fuel filter.
4) check the water filter.
5) check the starting battery.
6) start the generator and check if there is any effect.
7) use the air gun and the radiator at the front and rear ends of the water cooler.
B maintenance
1) repeat a class a daily and weekly examination.
2) replace the generator oil. (the oil replacement period is 250 hours or one month)
3) change the oil filter. (oil filter cartridge replacement period is 250 hours or one month).
4) replace the filter cartridge of the fuel filter. (the replacement period is 250 hours or a month)
5) replace the coolant or check the coolant. (the replacement period of the water filter element is 250-300 hours, plus in the cooling system.
Injection of supplemental coolant DCA)
6) clean or replace the air filter. (air filter replacement cycle is 500-600 hours)
C maintenance
1) replace diesel filters, oil filters, water filters, and replace water and oil in tanks.
2) adjust the tightness of the fan belt.
3) check the turbocharger.
4) dismantling, checking and cleaning PT pumps and actuators.
5) dismantle the cover of the rocker chamber and check the T-shaped pressure plate, valve guide and intake and exhaust valves.
6) adjust the lift of the nozzle and adjust the gap between the valve.
7) check the charging generator.
8) check radiator radiator and wash radiator external radiator.
9) add the tank inside the water tank and clean the inside of the water tank.
10) check the diesel engine sensor and connecting wire.
11) check the diesel engine instrument box.

About the author